POWERWALKER UPS VFI 6000P/RT HID(PS) (10120130) 6000 VA On Line Rackmount/Tower Version

POWERWALKER UPS VFI 6000P/RT HID(PS) (10120130) 6000 VA On Line Rackmount/Tower Version
Κατασκευαστής: POWERWALKER POWERWALKER
Κωδικός Προϊόντος: VFI 6000P/RT HID(PS)

PowerWalker VFI 6000 P/RT LCD

  • 6000VA / 5400W Online UPS with Power Factor 0,9
  • Terminal Input, 4x IEC C13 Outlet, 2x IEC C19 Outlet, Terminal Outlet
  • Backup time: 3,4min under full load and 9,8min under half load
  • 19inch rack design with LCD
  • Up to 2 units working in parallel also Battery Packs available

 
 
With true double-conversion online UPS design, PowerWalker VFI 6000RT provides powerful and overall protection to your sensitive devices. It can accept wide input voltage for harsh environment. It offers full protection for critical devices such as sensitive servers, network/telephone communication systems as well as for industrial applications.

With its slim design it only requires 3U valuable space of your rack system. The UPS can be installed in 19” rack systems or used as tower.

Technical specification

General features
Type Online
Power capacity 6000VA / 5400W
Output Power Factor 0.9
Input
Input Voltage Range 120-276 VAC Depends on Load Level
Max THDi <5%
Input PF ≥ 0.99 at full load
Frequency Range 45Hz - 55Hz or 54Hz - 66Hz
Frequency (Synchronized Range) 45Hz - 55Hz or 54Hz - 66Hz
Output
Nominal Output Voltage 208/220/230/240 VAC
Pure Sine Wave Yes
THDv ≤2% Full Linear Load; ≤5% Non-Linear Load
Voltage Regulation ±1%
Frequency (Battery Mode) ±0,2Hz
Parallel Work Up to 2 units of the same size
Technical details
Load Crest Ratio 3:1
Transfer Time [AC to Battery] 0ms
Transfer Time [Inverter to Bypass] 0ms
Transfer Time [Inverter to ECO] 1ms
Transfer Time [ECO to Inverter] 10ms
Bypass Before UPS Power-on: Default “No” Change to “Yes” via display panel
Overload und UPS Failure: Automatically transfer to bypass
By Setting: Voltage Rang: 120-276V ± 3%
Generator support Yes
Overload Capacity 2min @102%-130%; 30s @130%-150%; 100ms @ >150%
External Battery Connection Yes
Charger 1A
Fan Logic Always on, automatic speed control
LCD Indicators UPS status, Load level, Battery level, Input/Output voltage, AC mode, battery mode, Bypass mode, fault conditions; LCD Display colour : Blue, red, red flashing (depends on UPS status), direction swappable (rack/tower)
Efficiency
LINE mode full Load 93,3%%
BATTERY mode full Load 89,0%%
Energy Star compliance Yes
Batteries and autonomy time
Batteries 15x 12V/5Ah
Recharge Time 3h to 90%
Full Load Backup Time 3.4 min.
Half Load Backup Time 9.8 min.
Connections and communication
IEC C13 Outlet 4
IEC C19 Outlet 2
Terminal Output 1
Input Terminal
Software WinPower
USB Yes
RS-232 Yes
Intelligent Slot Yes, 1
Dry contact Yes
EPO Yes
Environment
Noise Level < 45dB
Temperature 0°C – 40°C
Humidity 0% - 95% RH (non-condensing)
Logistics
IEC 62040-3 classification VFI-SS-111
Package Content UPS, 2x IEC cable, EPO plug, manual, USB cable, Software CD, Tower holder, Rack ears, parallel communication cable
Manual Languages EN
EAN 4260074974713
Width 438 mm
Height 129 mm
Depth 698 mm
Weight 46 kg
Giftbox Width 955 mm
Giftbox Height 578 mm
Giftbox Depth 305 mm
Giftbox Weight 50 kg
Pcs. per box 1
Pcs. per layer 1
Pcs. per pal 7