POWERWALKER UPS VFI 10000TCP 3/1(PS) (10120161) 10KVA On Line 3F/1F

POWERWALKER UPS VFI 10000TCP 3/1(PS) (10120161) 10KVA On Line 3F/1F
Κατασκευαστής: POWERWALKER POWERWALKER
Κωδικός Προϊόντος: VFI 10000TCP 3/1(PS)

PowerWalker VFI 10000 TCP 3/1

  • 10000VA / 9000W Online UPS with Power Factor 0,9
  • Terminal Input, 2x IEC C13 Outlet, Terminal Outlet
  • Backup time: 3,9min under full load and 12,5min under half load
  • Compact tower design with LCD
  • Up to 4 units working in parallel also Battery Packs available

I
 
 

With its true double-conversion online UPS design, PowerWalker VFI 10000TCP 3/1 provides powerful and overall protection to your sensitive devices. With its 3 phase in and 1 phase out it can balance the power consumption from all incoming lines and creates a stable power output for equipment with even high power consumption. Multiple communication ports allow to integrate the UPS in existing structures.

Technical specification

General features
Type Online
Power capacity 10000VA / 9000W
Output Power Factor 0.9
Input
Input Voltage Range Voltage Range single phase
110-276VAC
Transfer Voltage Range based on Load percentage 100%/50%
Line low loss 176VAC/110VAC (±3%)
Line low comeback 186VAC/120VAC (±3%)
Line high loss 276VAC (±3%)
Line high comeback 266VAC (±3%)
Vo
Max THDi <5%
Input PF ≥ 0.99 at full load
Frequency Range 45Hz - 55Hz or 54Hz - 66Hz
Frequency (Synchronized Range) 45Hz - 55Hz or 54Hz - 66Hz
Output
Nominal Output Voltage 208/220/230/240 VAC
Pure Sine Wave Yes
THDv ≤2% Full Linear Load
Voltage Regulation ±1%
Frequency (Battery Mode) ±0,05Hz
Parallel Work Up to 4 units of the same size
Technical details
Load Crest Ratio 3:1
Transfer Time [AC to Battery] 0ms
Transfer Time [Inverter to Bypass] 0ms
Transfer Time [Inverter to ECO] 0ms
Transfer Time [ECO to Inverter] 10ms
Bypass Before UPS Power-on: Default “No” Change to “Yes” via display panel
Overload und UPS Failure: Automatically transfer to bypass
By Setting: Voltage Rang: 176-276V ± 3%
Generator support Yes
Overload Capacity 5min @100%-110%; 1min @110%-130%; 10s @130%-150%; 2s @>150%
External Battery Connection Yes
Charger 1.4A
Fan Logic Always on, automatic speed control
LCD Indicators UPS status, Load level, Battery level, Input/Output voltage, AC mode, Battery mode, Bypass mode, Fault conditions
Efficiency
LINE mode full Load 93,1%%
BATTERY mode full Load 92,0%%
Energy Star compliance Yes
Batteries and autonomy time
Batteries 20x 12V/9Ah
Recharge Time 8h to 90%
Full Load Backup Time 3.9 min.
Half Load Backup Time 12.5 min.
Connections and communication
IEC C13 Outlet 2
Terminal Output 1
Input Terminal
Software WinPower
USB Yes
RS-232 Yes
Intelligent Slot Yes, 1
EPO Yes
Environment
Noise Level < 55dB
Temperature 0°C – 40°C
Humidity 0% - 95% RH (non-condensing)
Logistics
IEC 62040-3 classification VFI-SS-111
Package Content UPS, manual, USB cable, Software CD
Manual Languages EN
EAN 4260074975574
Width 260 mm
Height 708 mm
Depth 550 mm
Weight 85 kg
Giftbox Width 720 mm
Giftbox Height 428 mm
Giftbox Depth 970 mm
Giftbox Weight 98 kg
Pcs. per box 1
Pcs. per layer 3
Pcs. per pal 6